Single-functions monitoring relays (AC voltage monitoring in 1-phase network - 1(N)~ 230 V). Monitoring of exceeding the Umin/Umax threshold, phase failure. Histeresis mode.
Adjustment of tripping delay. Cadmium - free contacts 1 CO and 2 CO. AC input voltages. Cover - modular, width 17,5 mm. Direct mounting on 35 mm rail mount acc. to EN 60715.
Technical data
Output circuit - contact data |
|
Number and type of contacts |
1CO, 2CO |
Contact material |
AgSnO2 |
Max. switching voltage |
300 V AC |
Input circuit |
|
Supply voltage AC |
= monitoring voltage |
Rated voltage |
≤ 1,3 W |
Range of supply frequency AC |
48...63 Hz |
Meassuring circuit |
|
Functions |
MINMAX - phase monitoring histeresis mode |
Ranges of voltage |
MIN - smooth adjustment: 75% MAX - smooth adjustment: 125% |
Time ranges of tripping delay |
step adjustment: (0,1 s; 1 s; 2 s ¸); 3 s; 4 s; 5 s; 6 s; 7 s; 8 s; 9 s |
Insulation |
|
Rated surge voltage |
4 000 V AC 1,2/50μs |
Insulation rated voltage |
500 V AC |
Overvoltage category |
III |
General data |
|
Mechanical life |
> 3 x 107 |
Electrical life |
> 0,5 x 105 12 A, 6 A, 250 V AC |
Ambient temperature - operating |
-20...+60 oC |
Functions
Minimum voltage monitoring (with delayed disconnection of contact R). If the voltage on one of the phases drops below the threshold Umin, then the time T2 - switching off of the operational relay R - starts timing out. At the same time the red diode E slow flashes. When time T2 elapses, the red diode E lights up permanently and the operational relay R is switched off. If the voltage on a given phase exceeds the voltage Umin increased by the value of hysteresis, then the red diode E goes off and the operational relay R is switched on.
Maximum voltage monitoring (with delayed disconnection of contact R). If the voltage on one of the phases rises above the threshold Umax, then the time T2 - switching off of the operational relay R - starts timing out. At the same time the red diode E fast flashes. When time T2 elapses, the red diode E lights up permanently and the operational relay R is switched off. If the voltage on a given phase is lower than voltage Umax minus the value of hysteresis, then the red diode E goes off and the operational relay R is switched on.
Phase failure monitoring (without delay for disconnection of contact R). A drop in any of the phases below the threshold Uoff = 0,6 Un (rated voltage) will immediately light up red diode E and immediately switch off the operational relay R.
MINMAX - Voltage monitoring between Umin and Umax values. When phases L1, L2, L3 are switched on - when the voltages of all phases are between the thresholds Umin and Umax, after approximately 500 ms (time T1) the green diode U lights up and the operational relay R is switched on.