DC arresters for photovoltaic systems RSP-T2-DC... series

Technical info

Applications:

• For the protection of low-voltage devices against lightning strikes and surges,

• For installation according to the lightning protection zone (LPZ) concept in LPZ 0-1,

• Designed in accordance with the IEC 61643-31:2018 standard.

Features:

• Surge protection devices protect against lightning-induced surges in solar systems (photovoltaic power systems),

• These units must be installed in parallel in DC networks that need to be protected and provide both common and differential protection modes,

• Their location is recommended at both ends of the DC power line (on the solar panel side and the inverter/transformer side), especially if the line is external and long.

Series description:

• RSP-T...-DC.../... is an SPD of class I+II, II for low-voltage power systems,

• Primarily installed in the main distribution cabinet,

• The surge protectors are equipped with high-energy MOV (metal oxide varistors) with special thermal disconnectors and associated fault indicators.

 

Electrical Parameters

 

RSP-T2 -DC/2P

 

Maximum continuous operating voltage Uc

1000 V DC

Nominal discharge current (8/20 μs) In

20 kA

Maximum discharge current (8/20 μs) Imax

40 kA

Protection level Up

4 kV

Response time

≤ 25 ns

Ambient temperature (operation)

-40...+80 °C 

Cross-sectional area of wires connected to terminals

1,5...25 mm² (solid) / 35 mm² (stranded)

Number of poles

Index

Commercial code

Number of poles

2617146

RSP-T2 -DC/2P

2-pole

2617147

RSP-T2 -DC/3P

3-pole

Ask for the details of the offer

I consent to the processing of my personal data by Relpol S.A. More information on the processing of personal data in the Privacy Policy*
I have read the Privacy Policy*